EXAMPLE · REFERENCE MODEL · model_sil/

A SIL 4 Computer-Based Interlocking (CBI) reference model for a mainline passenger railway station. The model spans system architecture, hardware decomposition, vital software components, deployment configuration, formal safety analysis under IEC 61508 / EN 50129 / EN 50128, and cybersecurity analysis under ISO/SAE 21434. It is the most demanding reference model in the repository, targeting the highest integrity level applicable to railway signalling.


Model scope

The model covers a single CBI at a two-platform station with a facing junction. The interlocking controls and supervises:

  • Two home signals (one per direction)
  • Two points machines (facing and trailing junction)
  • Three track circuit sections (approach, Platform 1, Platform 2)
  • One level crossing with automatically operated barriers

The CBI communicates with the signaller workstation over a management LAN, with trackside object controllers over an EN 50159 Category 2 field bus, and between its two processor channels over a dedicated cross-comparison Ethernet bus.

Standards applied:

  • IEC 61508:2010 — Functional safety of E/E/PE systems; risk graph parameters for SIL determination
  • EN 50129:2018 — Railway safety-related electronic systems; safety case structure
  • EN 50128:2011+A1:2020 — Railway software; SIL 4 V-cycle, formal methods, diverse programming
  • EN 50159:2010 — Railway safety communication; Category 2 (open transmission system, adversarial threat)
  • ISO/SAE 21434:2021 — Cybersecurity engineering (CAL 3)
  • NIS2 Directive (EU 2022/2555) — Critical infrastructure cybersecurity obligations

Architecture

InterlockingSystem (hardware PartDef)
└── InterlockingControlSoftware (software PartDef, isDeploymentPackage)
    │   ── vital partition (SIL 4, MPU-protected) ──────────────
    ├── VitalSoftwareBase (abstract, silLevel: 4)
    │   ├── RouteProcessor       ← route set/lock/release logic
    │   ├── ConflictChecker      ← formally-verified conflict matrix
    │   ├── PointsController     ← position command and detection
    │   ├── SignalController     ← aspect authority, 5-condition check
    │   └── SafetyCommLayer      ← EN 50159 Cat 2 framing
    │   ── non-vital partition ──────────────────────────────────
    └── DiagnosticMonitor        ← read-only health reporting

Deployed as: Deployment::Station1Interlocking
  ├── vitalProcessorA  ╲  2oo2D cross-comparison
  ├── vitalProcessorB  ╱  via VitalSafetyLink
  ├── objectController1  (home signals)
  ├── objectController2  (points + level crossing)
  ├── trackCircuit1/2/3
  └── softwareImage (7 SWC instances)

The 2oo2D architecture (two-out-of-two with diagnostics) means both processor channels independently compute every interlocking output. Any disagreement triggers an immediate fail-safe state — all signals to most-restrictive, all route locks preserved. This achieves the SIL 4 dangerous-failure-rate target of < 10⁻⁸ /h.


Hardware

Element Type Description
System::InterlockingSystem PartDef (hardware) Top-level CBI hardware; processorChannels, fieldBusBaudRate
System::Hardware::VitalProcessor PartDef (abstract, SIL 4) 2oo2D vital processor channel; cpuFreqMhz, ramKb, flashKb
System::Hardware::ObjectController PartDef Field object controller; drives signal heads, points machines, level crossing equipment
System::Hardware::TrackCircuitInterface PartDef Audio-frequency track circuit interface; reports occupancy to vital processor
System::Hardware::SignalOutputModule PartDef Signal aspect output; fail-safe to most-restrictive on power loss
System::Hardware::PointsDriveModule PartDef Points machine drive; detection circuit independent of drive circuit
System::Hardware::LevelCrossingModule PartDef Barrier control module; barrierCount, warningTimeS

Software components

Element SIL Description
System::Software::VitalSoftwareBase 4 (abstract) Abstract base for all vital SWCs; cyclic execution ≤ 20 ms, B-Method specification obligation
System::Software::RouteProcessor 4 Evaluates and locks route requests; checks section clear, no conflict, points confirmed, LX confirmed
System::Software::ConflictChecker 4 Formally-verified conflict matrix; per-cycle CRC check; read-only flash
System::Software::PointsController 4 Commands point machines; waits for positively-proved detection; continuous supervision
System::Software::SignalController 4 Clears signals only when all five conditions true simultaneously; returns to danger within one scan on any failure
System::Software::SafetyCommLayer 4 EN 50159 Cat 2 framing: 32-bit CRC, sequence numbers, timestamp, source/destination address
System::Software::DiagnosticMonitor non-vital Read-only health reporting; MPU-enforced boundary prevents writes to vital partition

Requirements

Safety (IEC 61508 / EN 50128)

ID Title SIL
REQ-SIL-SAFE-001 Conflict checker shall prevent any two conflicting routes from being simultaneously set 4
REQ-SIL-SAFE-002 Signal controller shall only clear a signal when all interlocking conditions are simultaneously verified 4
REQ-SIL-SAFE-003 Points controller shall verify detected position before reporting confirmation 4
REQ-SIL-SAFE-004 Signal clearance shall be conditional on level crossing barriers confirmed lowered 3

Architecture and software process

ID Title SIL
REQ-SIL-SW-001 CBI vital processing shall use 2oo2D voting architecture with diverse processor channels 4
REQ-SIL-SW-002 Vital software shall be developed by two independent diverse teams 4
REQ-SIL-SW-003 Vital logic shall be formally specified using B-Method with machine-checked invariant proofs 4
REQ-SIL-SW-004 Safety communication shall implement EN 50159 Category 2 safety codes 4

Security

ID Title
REQ-SIL-SEC-001 Operator commands shall be authenticated before reaching the vital processor (mTLS 1.3 + TPM 2.0)
REQ-SIL-SEC-002 Field bus commands shall include EN 50159 safety codes preventing replay and insertion

Safety analysis

HARA (IEC 61508 risk graph) identifies four hazardous events against three safety goals. The two highest-rated events use risk parameters Cd/Fb/Pb/W3, yielding a SIL 4 target.

ID Title Risk params SIL FTTI
SG-SIL-001 Prevent conflicting train routes set simultaneously — 4 50 ms
SG-SIL-002 Prevent signal clearance unless all route conditions verified — 4 50 ms
SG-SIL-003 Prevent signal clearance while level crossing barriers unconfirmed — 3 500 ms
HE-SIL-001 Signal cleared into occupied track section Cd/Fb/Pb/W3 → 4 —
HE-SIL-002 Conflicting routes set simultaneously Cd/Fb/Pb/W3 → 4 —
HE-SIL-003 Signal cleared with points not in proved position Cc/Fb/Pb/W3 → 4 —
HE-SIL-004 Signal cleared while level crossing barriers not confirmed Cc/Fb/Pa/W2 → 3 —

Fault Trees demonstrate that the 2oo2D AND gate achieves the SIL 4 quantitative target:

ID Top event Target Result
FT-SIL-001 Conflicting route set without detection < 10⁻⁸ /h ~2.5 × 10⁻⁹ /h ✓
FT-SIL-002 Signal cleared without all conditions satisfied < 10⁻⁸ /h ~4.0 × 10⁻⁹ /h ✓

FMEA tables cover 14 failure modes across the vital processor, safety communication subsystem, and trackside field equipment.


Security analysis

TARA-SIL-001 covers the operator workstation and field bus interfaces with 3 damage scenarios, 3 threat scenarios, 2 cybersecurity goals, and 3 security controls:

Threat Feasibility Control
Compromised maintainer workstation issuing unauthorised route commands (TS-SIL-001) medium mTLS 1.3 with TPM-bound certificates (SC-SIL-001)
Replay of captured field bus point-movement command (TS-SIL-002) low EN 50159 Cat 2 sequence numbers (SC-SIL-002)
DoS flood on cross-comparison bus disrupting 2oo2D synchronisation (TS-SIL-003) medium VLAN rate-limiting on cross-comparison bus (SC-SIL-003)

Test cases

Safety — SIL 4 interlocking (EN 50128)

ID Title Level
TC-SIL-SAFE-001 System integration — 2oo2 channel disagreement forces immediate safe state L5
TC-SIL-SAFE-002 System integration — signal reverts to red within one scan cycle when track section becomes occupied L5
TC-SIL-SAFE-003 Integration test — conflict checker blocks simultaneous conflicting route requests L4
TC-SIL-SAFE-004 Integration test — level crossing barriers must be confirmed down before signal clearance L4
TC-SIL-SAFE-005 Integration — PointsController position confirmation blocks signal clearance L4

Architecture and software process

ID Title Level
TC-SIL-SW-001 Software unit test — ConflictChecker conflict matrix formally verified L3
TC-SIL-SW-002 Integration test — EN 50159 Category 2 safety codes reject all defined fault classes L4
TC-SIL-SW-003 Inspection — Independent development process evidence for Channel A and B diversity L2

Security

ID Title Level
TC-SIL-SEC-001 Integration — Operator commands rejected without valid mTLS session L4
TC-SIL-SEC-002 Integration — EN 50159 Category 2 safety codes reject all defined fault classes on field bus L4

System integration

ID Title Level
TC-SIL-SYS-001 HIL — End-to-end system integration test for SIL 4 interlocking safe state L5

Running the validator

syscribe -m model_sil/ validate

The model produces 0 errors and 8 warnings, all advisory:

  • W030 (x2) on damage scenarios with safety impact but no hazardRef, and W032 on a cybersecurity goal whose CAL is below what its critical-risk threats require (security co-analysis findings);
  • W962 (x3) on damage scenarios that name no assets (ISO/SAE 21434 §15.3);
  • W056 (x2) on the Station1Interlocking connection endpoints vitalProcessorA.vitalDataPort / vitalProcessorB.vitalDataPort, which do not resolve to a member port.